Building Specs
We are located in
the Switch and Data Facility in Reston, Virginia.
The Reston data center is a one-story building located
in the dominant fiber corridor of the Vienna/Tyson’s Corner
area.
|
| |
|
| Square Feet |
15,256 |
| Ceiling Height |
Ten feet above raised floor |
| Roof Rights |
Roof rights available with
satellite space |
| Line of Site |
Clear line of sight in all
directions |
| NPA-NXX |
703-742 |
| Fiber Conduits |
Twelve 4-inch conduits |
| Fiber Innerducts |
Forty-eight innerducts and four
1-inch innerducts/conduit |
| KVM Cart |
KVM cart available upon request |
| |
|
 |
| |
|
|
Environmental Controls
|
| |
|
| Fire Supression |
Pre-action, dry pipe sprinkler
system |
| HVAC |
A/C units maintain a climate of
72 degrees (+/- 5) and 30-60% humidity, N+1 redundancy |
 |
| |
|
|
Power Systems
|
| |
|
| Power
Redundancy |
Space supports 100 Watts per
square foot; UPS size(s): 450 KVA UPS system; UPS system is N+1;
power redundancy throughout colo space via redundant UPS power
distribution units. 2400A DC Plant built to 2N+1 |
| Standby Generator |
750 KVA with a 1,500 gallon tank |
| |
|
 |
| |
|
|
Security Systems
|
| |
|
| Security
Systems |
Lobby security, real time video
surveillance provides 24x7 monitoring, mantrap, card key access,
alarm/key monitoring, and CCTV surveillance |
 |
| |
|
|
Connectivity
|
Multiple Data Providers |

 |
| |

|